Fire Extinguishing Systems

About Icons

  • Eco Mark (Type I)
  • Self-Declared Type (Type II)
  • RoHS Directive
  • PFOS (Chemical Substances Control Law)
  • CUD Mark

Inert Gas
Extinguishing Systems
Package-Type Inert Gas Fire Extinguishing System

NEO-Tandem

Features

NEO-Tandem

NEO-Tandem is a compact IG-541 fire extinguishing system developed for small areas. The IG-541 fire extinguishing system uses the revolutionary IG-541 gaseous fire extinguishing agent, which allows people to breathe. Composed of atmospheric substances, IG-541 has an ozone depletion potential of zero, and with a relative gravity of 1.07, it is an excellent gaseous extinguishing agent that maintains a steady extinguishing effect even after being released. The IG-541 fire extinguishing system has been adopted in many countries around the world, attesting to its global acceptance and the universal trust placed on it. NEO-Tandem saves space and cost by integrating the outstanding features of the IG-541 fire extinguishing system into a single package.


Safe for human beings
There is no risk of asphyxiation from inhaling the gaseous agent. Also, it ensures good visibility during evacuations, and does not generate toxic gases through decomposition.
Safe for the global environment
IG-541 uses substances that are naturally present in the atmosphere.
Safe for property
There is no metal corrosion from gaseous agents, and no frost or condensation caused by evaporative cooling.
Excellent extinguishing performance
IG-541 has a relative gravity to air of 1.07 (standard relative gravity after release), making it difficult for the gas to escape outside the fire hazard area after being discharged, ensuring steady fire suppression.
A fire extinguishing system that has been recognized around the world
The IG-541 fire extinguishing system is a globally accepted system introduced in many countries around the world.
Easy-to-understand display panel
The graphic panel allows you to grasp the operation status at a glance.
Buffers operation history for viewing
Since the operation status at the time of a fire or fault is buffered in the main unit, the history can be easily accessed by connecting to a PC.
Improved noise resistance
The system’s noise resistance properties comply with international standards (IEC standards*).* IEC61000-6-2 immunity (noise immunity) standard for industrial environments

Specifications

Approval No. 109 (FESC-approved)
Product Name Main Type for 1 Unit Main Type for 2 Units
Model Code NTH-A-I83-1(-CV) * NTH-A-I83-2(-CV) *
Total System Weight Approx. 305 kg Approx. 460 kg
Extinguishing Agent Type IG-541
Extinguishing Agent Cylinder Type (Volume) 83 L
Effective Discharge Volume (20°C) 22.6 m³
Extinguishing Agent Cylinder Material: CrMo steel, etc.; Hydrostatic test pressure: 50 Mpa; Coating color: gray
Cylinder Valve Approval No.: Yo-192 Model Code: IR-12
Box Dimensions W500×
D400×H2,060 mm
W700×
D400×H2,060 mm
Box Construction Single, front opening (t=2.3 mm)
Box Coating Coating Color: Oyster gray (C25-80A, semi-glossy) or designated color
Operating Temperature Range 0°C to 40°C
Operating Humidity Range 85%RH or less (with no condensation)
Voice Alarm System AA-039
(FESC-approved)

* If with a shut-off valve, model code has “-CV” added at the end

Approval No. 109 (FESC-approved)
Product Name Subtype for 1 Unit Subtype for 2 Units
Model Code NTH-EX-I83-1 NTH-EX-I83-1-SV NTH-EX-I83-2 NTH-EX-I83-2-SV
Activation Device Without With Without With
Interlocking Method with Main Type Gas pressure interlock Electric interlock Gas pressure interlock Electric interlock
Total System Weight Approx.
270 kg
Approx.
300 kg
Approx.
425 kg
Approx.
455 kg
Extinguishing Agent Type IG-541
Extinguishing Agent Cylinder Type (Volume) 83 L
Effective Discharge Volume (20°C) 22.6 m³
Extinguishing Agent Cylinder Material: CrMo steel, etc.; Hydrostatic test pressure: 50 Mpa; Coating color: gray
Cylinder Valve Approval No.: Yo-192 Model Code: IR-12
Box Dimensions W500×
D400×H2,060 mm
W700×
D400×H2,060 mm
Box Construction Single, front opening (t=2.3 mm)
Box Coating Coating Color: Oyster gray (C25-80A, semi-glossy) or designated color
Operating Temperature Range 0°C to 40°C
Operating Humidity Range 85%RH or less (with no condensation)
Voice Alarm System

Electrical Specifications, etc.

Discharge Activation Method Main type: Automatic/manual selector switching; Sub type is operated by main type
Detector Circuit 2 lines, AND circuit
Voice Alarm System 3-channel voice synthesis Confirmation number: AA-039 (*Refer to 3/3 in Specifications)
Delay Timer Can be set between 0–99 seconds (standard setting: 20 seconds)
Monitor Functions Indicator lamp flashing, buzzer sounds, fault relays
[1] Detection of sensor open circuit
[2] Detection of ground fault
[3] Detection of manual discharge line short-circuit
[4] Detection of battery power supply AC power shutoff
[5] Voltmeter (displays voltage of battery power)
[6] Battery test (checks of battery power voltage during normal times)
Display Panel Power indicator lamp
System activation indicator lamp
Auto indicator lamp
Power failure indicator lamp
Detector 1 activated indicator lamp
Discharge indicator lamp
Detector 1 disconnected indicator lamp
Charging indicator lamp
Detector 2 activated indicator lamp
Shut-off valve open indicator lamp (*1)
Detector 2 disconnected indicator lamp
Pre-discharge indicator lamp
Shut-off valve closed indicator lamp (*1)
Electric ground fault indicator lamp
Fire indicator lamp
Manual indicator lamp
Short-circuit indicator lamp
Recovery switch
Buzzer stop switch
Automatic/manual selector switch
Battery test switch
Buzzer: Goes off in case of fire hazard, system activation, manual activation station or alarm door open, activation of detector 1 or 2, or fault
Alarm door: Evacuation announcement is triggered when door is opened; the fire and pre-discharge indicator lamps light up
Discharge push button: Pressing this button activates a delay timer, and the gas is released after the timer runs out
Relay Contact [1] Fire relay: Form C contact x 1
[2] Discharge relay: Form C contact x 1
[3] Automatic/manual relay: Form C contact x 1
[4] System activation relay: Form C contact x 1
[5] Fault relay: Form C contact x 1
[6] Shut-off valve closed relay: Form C contact x 1
[7] Machine stop relay: Form C contact x 3
[8] Detector 1 activation relay: Form A contact x 1
[9] Detector 2 activation relay: Form A contact x 1
[10] Power failure relay: Form A contact x 1
[11] Machine stop: Form C contact x 2
Contact Specifications [1] – [7]: DC30 V, 1 A
[8] – [10]: AC250 V, DC30 V, 1 A
[11]: AC250 V, DC30 V, 2 A
Input Signal
Detector 1 Input NITTAN photoelectric spot type smoke detector: 2KH3 Max. number of connections: 30
OKI photoelectric spot type smoke detector: HSS220EGD Max. number of connections: 20
(No restrictions on heat detectors as long as they are contact-type)
Detector 2 Input
Shutter Close Input Shutter “closed” confirmation signal input (must be a non-voltage Form A contact input)
Output Signal
Shutter Close Output DC24 V/1 A (Protective fuse)
Discharge Signal Output DC24 V/5 A (Protective fuse)
Speaker Audio output of voice alarm system, up to 20 W
Solenoid Actuator Model Code: R72
Pilot Cylinder Volume 1.0 L/Filled gas weight 0.65 kg
Circuit Voltage DC24 V
Power Consumption Max. 10 W (0.1 A for monitoring, 0.4 A for operation, excluding external devices)
Emergency Power Supply Battery power supply system manufactured by Nippon Dry-Chemical (certified product)
[1] Battery capacity: 6.5 Ah Power supply: AC100 V Model: EPTII06
[2] Battery capacity: 15 Ah Power supply: AC100 V Model: EPTII15