1. Home >
  2. Extinguishing Systems for Manufacturing Equipment >
  3. CABINEX Series >
  4. CABINEX-EN2

CABINEX-EN2

  • COX-7EN2

    COX-7EN2

Below is a typical installation drawing for Cleaning Equipment.

Explanation of each part of the Cabinex system.

 (1) CABINEX Body・Main : to contain CO 2 Cylinder and Control Panel. It should be selected in accordance with the volume of extinguishing chemical agent required.
 (2) CABINEX Body・Sub : to contain only CO 2 Cylinder which is discharged together with Main’s simultaneously.
 (3) TH Sensor : Heat Detector at 70℃. Hatsuta’s original sensor.
 (4) Infrared Sensor : Flame Detector. Hatsuta’s original sensor.
 (5) Nozzle : Total flooding system.

  • Example

  • Cabinex EN2 is for FPD, SEMI, and Machininf tool.

    We can drsign based on your machine.You can choose lots of Options.

  • Fire Detection Setup:

    ・ Selectable between “AND” function and “OR”function.
    ・ No limitation to combination of types of sensors.
    ・ Small sensors(developed by HATSUTA)available.

  • Flexible Installation and Functional Setup:

    ・ Selectable between “Automatic” and “Manual” operation modes.
    ・ Selectable between “all-in-one” combined unit and separated units of Operation Panel and Extinguishing Agent Container.

  • Self-Supervision and Safety Precaution:

    ・ Automatic alarm indication of possible fault(s) in the sensors(s) and of pressure reduction in the Extinguishing Agent Container.

  • Service Network

    Hatsuta has our service network not onlr in Japan, but also in Asia Countries, USA.Hatsuta's network can answer your request, as installation, maintenance, CO2 refill as well as Emergency.Please do not hesitate to contact us or our service representatives. We are always eager to help our customers..

Specification
  Integrated Type
Certification No. COX-3EN2COX-5EN2COX-7EN2COX-14EN2COX-18EN2
Main Chasis & Container External Dimentions
(H×W×D)mm
760×290×180920×320×215920×320×215 1,160×400×300 1,160×400×300
Weight Approx. 23kgApprox. 35kgApprox. 37kgApprox. 86kgApprox. 90kg
Fire Extinguishing Agent Carbon Dioxide ( CO2 )
Weight of the Fire Extinguishing Agent 3.2kg4.6kg6.8kg14.0kg18.0kg
Coating Specifications Coating Color : Red Melamine Baking Finish, Japaning
Material Steel ( SPCC ) t=1.2mmSteel ( SPCC ) t=1.6mm
Operating Temperature Range 0℃~+40℃
Control Function Input Supply Voltage Range 100V, 110V, 200V, 220V, AC 50/60Hz ( With Each Voltage Terminal )
Power Cunsumption 24VA Max.
Operation Circuit Voltage 24V DC
Sensor Input Circuit 2 System ( AND / OR Operation Selection System )
Push Button for Start-Up Red Push Button ( With Breaking Acrylic Plate )
Reset Button White Push Button
Automatic/Manual Operations Selector Switch The Fire Extinguisher can be Operated with a Sensor Input Signal in the Automatic Mode
Alarm Buzzer Electronic Buzzer ( Continuous Sound in Case of Fire、Intermittent Sound in Case of Abnormal Condition )
Buzzer Stop Switch Stops the Intermittent Sound in Case of Abnormal Condition ( The Continuous Sound in Case of a Fire Cannot be Stopped )
Power Indicator Lamp Green LED
Auto Indicator Lamp Green LED ( Light Up in the Auto Mode )
Fire Indicator Lamp Red LED ( Flashing in Case of Fire )
Discharge Indicator Lamp Red LED ( Flashing when Discharge )
Fault Indicator Lamp Yellow LED ( Flashing at start-up unit failure, sensor wiring line suspended )
Barn-out Indicator Lamp Red LED ( Flashing at Sensor Wiring Line Suspended )
Unit Failure Indicator Lamp Red LED ( Flashing When the Start-Up Unit Connector is not Connected Yet )
Reduced Pressure Indicator Lamp Red LED ( Flashing When the Fire Extinguishing Container Inner Pressure Drops )
Buzzer Stop Indicator Lamp Red LED ( Flashing at Buzzer Stop )
Fire Annunciating Contact Contact c×1( Contact Switches at Sensor Alarm
Machine Stop Contact Contact c×1, Contact a×1, Contact b×1( Contact Switches at AC Power Down
Power Failure Annunciating Contact Contact c×1( Contact Switches at Discharge
Fault Annunciating Contact Contact c×1( Contact Switches at Fault, except Start-Up Unit Connection Fault
Automatic/Manual Annunciating Contact Contact c×1( Manual Mode B-B2 is Closed, Auto Mode B-B1 is Closed
Contact Specification Contact Capacity : 60W/125VA Max. Maximum Current: 1A Maximum Voltage: 250V AC/200V DC
Battery Ni-Cd battery/24V DC/0.45Ah/5hours
Timer Delayable up to 10 seconds
Remote start
(Manual Release)
Possible to actuate by remote push button
Specification
  Separate Type Control Unit
Certification No. CPX-REN2CPX-UEN2
Main Chasis & Container External Dimentions
(H×W×D)mm
340×280×90220×340×130
Weight Approx. 6kgApprox. 6.3kg
Fire Extinguishing Agent Carbon Dioxide ( CO2 )
Weight of the Fire Extinguishing Agent -
Coating Specifications Coating Color : Red Melamine Baking Finish, Japaning
Material Steel ( SPCC ) t=1.6mm
Operating Temperature Range 0℃~+40℃
Control Function Input Supply Voltage Range 100V, 110V, 200V, 220V, AC 50/60Hz ( With Each Voltage Terminal )
Power Cunsumption 24VA Max.
Operation Circuit Voltage 24V DC
Sensor Input Circuit 2 System ( AND / OR Operation Selection System )
Push Button for Start-Up Red Push Button ( With Breaking Acrylic Plate )
Reset Button White Push Button
Automatic/Manual Operations Selector Switch The Fire Extinguisher can be Operated with a Sensor Input Signal in the Automatic Mode
Alarm Buzzer Electronic Buzzer ( Continuous Sound in Case of Fire、Intermittent Sound in Case of Abnormal Condition )
Buzzer Stop Switch Stops the Intermittent Sound in Case of Abnormal Condition ( The Continuous Sound in Case of a Fire Cannot be Stopped )
Power Indicator Lamp Green LED
Auto Indicator Lamp Green LED ( Light Up in the Auto Mode )
Fire Indicator Lamp Red LED ( Flashing in Case of Fire )
Discharge Indicator Lamp Red LED ( Flashing when the Start-Up Unit Operates )
Fault Indicator Lamp Yellow LED ( Flashing at Start-Up Unit Failure, Sensor Wiring Line Suspended and Fire Extinguishing Agent Container Reduced Pressure )
Barn-out Indicator Lamp Red LED ( Flashing at Sensor Wiring Line Suspended )
Unit Failure Indicator Lamp Red LED ( Flashing When the Start-Up Unit Connector is not Connected Yet )
Reduced Pressure Indicator Lamp Red LED ( Flashing When the Fire Extinguishing Container Inner Pressure Drops )
Buzzer Stop Indicator Lamp Red LED ( Flashing at Buzzer Stop )
Fire Annunciating Contact Contact c×1
Machine Stop Contact Contact c×1, Contact a×1, Contact b×1
Power Failure Annunciating Contact Contact c×1
Contact Specification Contact Capacity : 60W/125VA Max. Maximum Current: 1A Maximum Voltage: 250V AC/200V DC
Timer Delayable up to 10 seconds
Specification
  Separate Type
Model COX-7ENS2COX-14ENS2COX-18ENS2
Main Chasis & Container External Dimentions
(H×W×D)mm
920×320×215 1,160×400×300 1,160×400×300
Weight Approx. 36kgApprox. 84kgApprox. 88kg
Fire Extinguishing Agent Carbon Dioxide ( CO2 )
Weight of the Fire Extinguishing Agent 6.8kg14kg18kg
Coating Specifications Coating Color: Red Melamine Baking Finish, Japaning
Material Steel ( SPCC ) t=1.2mmSteel ( SPCC ) t=1.6mm
Operating Temperature Range 0℃~+40℃
Unit Product Code 60050299-
Maitenance valve With Out
Specification
  Separate TypeSub Type
Model COX-30ENA2COX-45ENA2COX-30ENA2-SCOX-45ENA2-S
Main Chasis & Container External Dimentions
(H×W×D)mm
1,755×400×330 1,915×525×380 1,755×400×330 1,915×525×380
Weight Approx. 140kgApprox. 180kgApprox. 140kgApprox. 180kg
Fire Extinguishing Agent Carbon Dioxide ( CO2 )
Weight of the Fire Extinguishing Agent 30kg45kg30kg45kg
Coating Specifications Coating Color: Red Melamine Baking Finish, Japaning
Material Steel ( SPCC ) t=1.6mm
Operating Temperature Range 0℃~+40℃
Maitenance valve WithWith Out
  • CALUMIE
  • CABINEX Series
  • Argonite Amulay 30
  • ECOSS pure water
  • SUPER OWL
  • METAX
  • Replacement Parts for CABINEX

▲ top of page